Results
Voltage drop
Voltage drop
- Good (under 3%)
- Borderline (3–5%)
- Too high (5%+): use thicker wire
How it works
Vdrop = k × L × I × R ÷ 1,000Current flows out and back, so a single-phase or DC circuit has twice the one-way length of wire (k = 2); three-phase uses k = √3. Resistance per 1,000 ft comes from the National Electrical Code (Chapter 9, Table 8, at 75 °C). A common target is no more than 3% drop on a branch circuit, so lights don’t dim and motors don’t strain. If the drop is too high, go up a wire size.
-
Look up the resistance per 1,000 ft
12 AWG → 1.93 Ω per 1,000 ft -
k × L × I × R ÷ 1,000
2 × 100 ft × 15 A × 1.93 ÷ 1,000 = 5.79 V -
As a share of the supply
5.79 ÷ 120 × 100 = 4.83% -
Good to know
- For sizing real installations, follow the NEC and local code; this checks voltage drop only, not ampacity.